Guide · Electrical and lighting · Tensile strength classes, nylon 6/6 vs UV black vs stainless, UL 62275 and NEC 300.11 and 725, tie-wire and banding

Bayshore Safety & Industrial Supplies Guide

Cable ties explained: tensile strength classes from 18 to 250 lb, length and bundle size, nylon 6/6 vs UV black vs heat-stabilized vs stainless, the UL 62275 types and NEC rules for securing cable, tie-wire and banding tools? Miniature, intermediate, standard and heavy-duty classes, why natural nylon chalks outdoors and black UV nylon does not, temperature ratings, plenum and halogen-free ties, NEC 300.11 and 725.24 on support, the 21 and 1C rating codes, releasable and mounting-head ties, and the installation tool and flush cut rule

A cable tie is specified by four things on the bag: tensile strength (the loop tensile strength in pounds under UL 62275 and the older UL 1565: miniature 18 lb, intermediate 40 lb, standard 50 lb, heavy 120 lb, extra heavy 175 lb and 250 lb, with 30, 75 and 100 lb in between from some makers), length (4 to 60 inches, which sets the maximum bundle diameter; a tie needs 2 to 3 inches more length than the bundle circumference to feed and pull), width (0.1 to 0.5 inch, following the strength class), and material. Nylon 6/6 natural (white or clear): the general-purpose tie, -40 to 185 °F, absorbs moisture (which keeps it flexible; a dried-out tie snaps) and degrades in sunlight within a season, so it is an indoor tie. UV-stabilized black nylon 6/6 (carbon black loaded, the UVB and UV suffixes): the outdoor tie, rated for continuous sun exposure, same strength and temperature. Heat-stabilized nylon (HS, 221 to 257 °F) for engine compartments and hot panels; impact-modified and cold-weather nylon for installation below freezing; halogen-free and plenum-rated (UL 94 V-2 at least, with the plenum CMP designation when run in air-handling spaces); flame-retardant for rail and transit; polypropylene for chemical resistance; detectable blue ties for food plants; fluoropolymer (Tefzel) for radiation and chemicals. Stainless steel ties (304 for general outdoor, 316 for marine and chemical; coated with nylon or polyester where the band would cut insulation) for high temperature, fire survivability, solar and anywhere nylon fails, applied with their own tension tool. The electrical code sets where a tie is allowed to be the support: NEC 300.11(A) requires raceways, cable assemblies and boxes securely fastened in place and (B) prohibits using the support wires of a suspended ceiling, and NEC 725.24, 760.24, 770.24 and 800.24 require low-voltage, fire alarm, optical fiber and communications cables supported so that the cable is not damaged by normal building use and listed cable ties where used in plenums; UL 62275 lists ties by type (Type 1 nylon, Type 2 and 21 for support under NEC (the 21 and 21S ratings mean the tie was tested as a cable support in plenums and the S for stainless), with the 1C code for UV outdoor and 2 for continuous heat) and the local inspector reads the bag for the UL mark and the rating. Tie-wire (16 gauge annealed, black annealed and galvanized, and 18 gauge, on reels and in 3.5 pound rolls) ties rebar and lath and hangs duct and conduit where the code allows wire support; banding (stainless strap and buckles with the Band-It tool) clamps sign posts, hose and pole-mounted equipment; the guide covers both because the shop stocks them together. Installation: the tie is tensioned with a tie tool set to the strength class and cut flush, because a hand-cut tail is a sharp edge that opens hands (the glove guides have the injury), and a tie is not reused unless it is a releasable type. The band lists the cable ties by strength and material, tie-wire, banding and tools we stock.

Bayshore Safety. Industrial safety and PPE supplier since 2017. · Current as of November 2026 · UL 62275 (Cable management systems, cable ties for electrical installations) and the former UL 1565 (Positioning devices); UL 94 flammability; NFPA 70, National Electrical Code, 300.11 (securing and supporting), 725.24, 760.24, 770.24 and 800.24 (support of cables), 300.22 (ducts and plenums); the Gardner Bender, Anchor Brand, Panduit, Thomas & Betts, Ideal, Band-It and Precision Brand product data on this site (tensile strength, length, bundle diameter, material, temperature, UL rating as printed)

Why the white ties on the fence fell off in a year and the black ones are still there. Natural nylon turns chalky and brittle in sunlight; carbon black absorbs the UV before it reaches the polymer, and that one additive is the difference between an indoor and an outdoor tie. The cards cover the strength classes and sizing, the materials, the code rules on using a tie as cable support, the UL ratings on the bag, tie-wire and banding, and the installation tool.

Cable ties, question by question

The strength classes and ratings are UL 62275; the support rules are the NEC; the material limits are the makers’ data sheets.

What do the pound ratings mean, and which class for which job?The loop tensile strength: the force at which a closed loop of the tie breaks in the UL test, not the pull-through strength of the head alone. Miniature 18 lb (4 inch, 0.1 inch wide): wire harnesses, small bundles, tagging. Intermediate 30 to 40 lb (5.5 to 8 inch): light bundles, signs, netting. Standard 50 lb (7 to 14 inch, 0.19 wide): the general tie for cable bundles to 4 inch, fence, temporary fixings. Heavy 120 lb (8 to 48 inch, 0.3 wide): conduit and tray bundles, hose, banner and fence. Extra heavy 175 lb (14 to 60 inch, 0.35 wide): large bundles, pole mounting, outdoor fixtures. 250 lb (0.5 wide): the largest nylon class before stainless. The rating is at room temperature on a new tie; cold, heat, UV, moisture loss and chemicals reduce it, and a tie carrying a load is sized two classes up from the calculated pull. For a bundle, the tie supports the weight between supports; for a sign or an object in wind, the tie takes the whole load and stainless is the usual answer.
How do I pick the length?Length minus the head and the tail needed to pull is the maximum bundle circumference; the makers print a maximum bundle diameter for each length (4 inch to 7/8 inch, 8 inch to 2 inch, 11 inch to 3 inch, 14 inch to 4 inch, 24 inch to 7 inch, 36 inch to 10 inch, 48 inch to 14 inch), and a tie needs 2 to 3 inches more than the circumference so the tool or the hand can grip the tail. Too short does not close; too long wastes tie and leaves a long cut tail. Ties are joined head to tail for a bundle larger than any single tie, at a loss of strength at the joints. Width follows the class and is the bearing surface on the cable jacket: a narrow high-tension tie cuts into a soft jacket, so for low-voltage, fiber and coax the installer uses a wider tie or a hook-and-loop strap at light tension, which is also the TIA and BICSI rule for data cable (ties loosely enough to turn by hand, no deformation of the jacket).
Nylon 6/6, black UV, heat-stabilized or stainless?Nylon 6/6 natural: indoor, -40 to 185 °F continuous, absorbs 2 to 3 percent moisture to stay flexible, becomes brittle if stored dry and hot (the bag is kept sealed; brittle ties are soaked overnight), degrades under UV in months. UV-stabilized black: 2 percent carbon black, outdoor and sunlight rated, otherwise the same; a black tie that is not marked UV is dye only, so the bag must say UV. Heat-stabilized (HS): 221 to 257 °F for panels, engine compartments and near lighting. Impact-modified and cold-weather: install down to -40 °F without cracking. Flame-retardant (UL 94 V-0) and halogen-free low-smoke for plenums, rail, transit and data centers; plenum support ties carry the UL 21 rating. Polypropylene: resists acids, bases and salt, lower strength, floats. Detectable and metal-detectable (blue, with a metal additive) for food and pharmaceutical plants. Tefzel ETFE: chemicals, radiation, 302 °F. Stainless 304 and 316, bare or nylon-coated, with ball-lock or ladder heads: high temperature (to 1,000 °F bare), fire survivability (the ties in a fire-rated cable run must not be the first thing to fail; NEC 300.11 and the fire codes), solar arrays, marine, chemical plants, pole mounting, anywhere a failed tie drops a cable; 316 for salt and chlorides.
When can a cable tie be the support, per the NEC?NEC 300.11(A): raceways, cable assemblies, boxes, cabinets and fittings securely fastened in place; (B): the wires that support a suspended ceiling are not to be used to support raceways, cables or boxes unless an independent support wire is added and marked. 725.24 (Class 2 and 3 circuits), 760.24 (fire alarm), 770.24 (optical fiber), 800.24 and 805 (communications): cables installed in a neat and workmanlike manner, supported by the building structure in such a way that the cable is not damaged by normal building use, using straps, staples, cable ties, hangers or similar fittings designed and installed so as not to damage the cable, with the informational notes citing ANSI/NECA/BICSI 568 and the listing requirement that ties used in plenums be listed for the purpose (UL 62275 Type 21 or the 2G rating for plenum). Power cable (NM, MC, AC) is supported at the intervals in its article (334.30, 330.30) by staples, straps, hangers or listed fittings; a cable tie counts where it is listed as a cable tie for the support and the AHJ accepts it, and nylon ties in a plenum must be the plenum-rated ones. A tie is never the support for a raceway, a box or a luminaire by itself (410.36 for luminaires; 314.23 for boxes), and the inspector reads the bag.
What do the UL codes on the bag mean?UL 62275 (harmonized with IEC 62275; replaced UL 1565 and CSA C22.2 No. 62275 in Canada) lists ties by type and rating: Type 1 is a general-purpose tie for bundling (not a support), Type 2 is rated for mechanical support of cable under the NEC articles above, Type 21 (and 21S for stainless) is rated for support in plenums and air-handling spaces with the smoke and flame test, and the subcodes give the environment: 1 (indoor), 1C (indoor and outdoor UV exposure), 2 (resistant to continuous heat as marked), and 2G (plenum, no PVC). A bag marked UL 62275 Type 2 1C is an outdoor-rated support tie; Type 1 with no code is a bundling tie for indoor use only; and a tie with no UL mark is not accepted as a support on an inspected job. Temperature rating, minimum installation temperature and tensile strength are printed beside the code.
Tie-wire, rebar ties and bandingTie-wire: 16 gauge black annealed (the rebar standard, 0.0625 inch, soft so it twists by hand or pliers, rusts to match the bar), galvanized and stainless where corrosion matters (concrete exposed to chlorides, stucco lath, exterior fence), 18 gauge for lath and light work, on 3.5 pound rolls for the belt reel (Klein and Ideal reels) and coils; pre-tied loop ties and bag ties in 4 to 8 inch for rebar with a twister tool, and rebar tying tools (battery) for production. Mechanics wire (annealed, 14 to 18 gauge) for hanging and safety wire; music wire (hard, spring temper) is not tie wire. Banding: stainless 201 and 316 strap in 1/4 to 3/4 inch with buckles, tensioned and cut with a Band-It or Strapbinder tool, for sign posts, pole-mounted boxes, hose clamps, insulation jacketing and anything a cable tie cannot carry; the band clamp hand tool crimps preformed clamps. Hook-and-loop straps (reusable, light tension) for data cable and anything that will be changed; releasable nylon ties for bundles that will be serviced; mounting-head and screw-mount ties and adhesive mounts for fixing a bundle to a surface; identification ties with a flag for labeling.
Installing and cuttingThe tie goes around the bundle, the tail through the head, pulled snug by hand and then tensioned with a cable tie tool (Gardner Bender, Panduit, Ideal) set to the class so the tie is tight without cutting the jacket, and the tool cuts the tail flush with the head; hand-cut tails with diagonal pliers leave a sharp stub that cuts hands, a known laceration cause in panels and trays, and a flush cutter or the tool is the rule in most electrical contractors’ safety programs (the hand protection guides). Ties are spaced at the intervals the cable article or the data standard calls for (every 12 to 18 inches in trays, closer at bends and transitions), never over-tightened on coax, fiber or data cable, not reused once cut, installed above the minimum temperature on the bag, and inspected on outdoor runs each season for chalking, cracking and broken heads; a tie that has gone white or chalky is replaced with UV black or stainless.

In plain words

  • The pound rating is the loop breaking strength: 18 miniature, 50 standard, 120 heavy, 175 extra heavy, 250 top nylon class; size two classes above the real pull.
  • Length sets the bundle size; allow 2 to 3 inches of tail.
  • Natural nylon indoors; black UV outdoors; heat-stabilized for hot panels; stainless for fire, heat, solar and anything a failed tie would drop.
  • A tie is a cable support only where the NEC article allows it and the bag carries the UL 62275 Type 2 or 21 rating; plenums need the plenum rating.
  • Tie-wire for rebar and lath; banding for posts and poles; hook-and-loop for data cable.
  • Tension with the tool and cut flush; hand-cut tails cut hands.

Questions people ask

What does the lb rating on cable ties mean?

The loop tensile strength at which a closed tie breaks under UL 62275; 18 lb miniature, 50 lb standard, 120 lb heavy, 175 lb extra heavy, 250 lb the largest nylon class.

Are black cable ties UV resistant?

Only if the bag says UV-stabilized; carbon-black UV nylon is rated for sunlight, dyed black natural nylon is not.

Can cable ties be used to support electrical cable?

Where the NEC article for that cable allows ties and the tie is listed under UL 62275 as Type 2 (or Type 21 in plenums); general-purpose Type 1 ties are for bundling.

What temperature are nylon cable ties rated for?

Natural and UV nylon 6/6 about -40 to 185 °F continuous; heat-stabilized to 221 to 257 °F; stainless far higher.

What size cable tie for a 2 inch bundle?

About an 8 inch tie (the maker’s maximum bundle diameter for 8 inch is about 2 inches), with 2 to 3 inches of tail to pull.

Why should cable tie tails be cut flush?

A hand-cut tail is a sharp stub that lacerates hands in panels and trays; the tie tool tensions and cuts flush.

The ratings, test results and standards shown here are the manufacturers' published values, reproduced as published. Nothing on this page is a recommendation by Bayshore Safety that any product is suitable for a particular task, hazard or workplace. Selecting safety products and protective equipment is the responsibility of the end user and the employer, based on their own hazard assessment and the regulations that apply to their work. Confirm every value on the manufacturer's own documentation before use.

Stocking an electrical or maintenance crew?Call (925) 215-7337 or email us the sizes, the environment (indoor, outdoor, plenum, high heat) and the quantities and we will quote cable ties, tie-wire and banding by the case with the part numbers listed. We sell nationwide.
All electrical and lighting guides

© 2026 Bayshore Safety & Industrial Supplies, Inc. All rights reserved. This guide may not be copied or republished without written permission.

How to buyCard, purchase order or invoice terms; quotes on request; agencies and institutions welcome.
Live Service & SupportReal people who know the products, Monday to Friday 7:30am to 4pm Pacific. 925-215-7337
We DeliverWe ship nationwide. Parcel and LTL freight to job sites and businesses across the U.S.