Extension cord gauge and length by amperage, and what OSHA requires on a jobsite cord? Reading the cord jacket (12/3 SJTW), the NEC ampacity table, voltage drop over 50 and 100 feet, why a 16 gauge cord starves a saw, hard vs junior hard service, the no-splice and no-doorway rules, GFCI protection, and inspecting the plug, jacket and ground pin

An extension cord is read off its jacket: 12/3 SJTW means 12 AWG conductors, three of them (hot, neutral, ground), in a junior hard service (SJ) thermoplastic (T) weather-resistant (W) jacket. The gauge sets how much current the cord can carry and how much voltage it loses over its length. NEC Table 400.5(A)(1) gives the ampacity for flexible cord with three current-carrying conductors: 18 AWG 7 amps, 16 AWG 10, 14 AWG 15, 12 AWG 20, 10 AWG 25 (the two-conductor column is higher; the cord maker prints the rating on the tag). Length then takes voltage: the makers’ charts, built on the NEC’s 3 percent recommended drop, put a 15 amp tool on 14 AWG to 50 feet and 12 AWG to 100 feet, a 20 amp tool on 12 AWG to 50 feet and 10 AWG to 100, and keep 16 AWG for lights and loads under 10 amps and short runs; a tool on a cord too light for it runs hot, loses torque and burns its motor. OSHA’s construction rules: 1926.405(a)(2)(ii)(J) requires extension cords used with portable tools to be three-wire and designed for hard or extra-hard usage (types S, ST, SO, STO, SJ, SJO, SJT, SJTO and their W-marked outdoor versions; household lamp cord is not allowed); 1926.405(a)(2)(ii)(I) requires cords protected from damage and not run through doorways and pinch points unless protected; 1926.405(g)(2)(iii) allows no splices or taps except a repair on a 12 AWG or larger cord that restores the original insulation; 1926.404(b)(1) requires GFCI protection or an assured equipment grounding conductor program for every cord set on a site; and 1926.416(e) and 1910.334(a) require cords inspected before use and removed when the jacket is cut, the plug is damaged or the ground pin is missing. The band lists the cords, GFCI cords and adapters, plugs and cord reels we stock by gauge and length.

Bayshore Safety. Industrial safety and PPE supplier since 2017. · Current as of November 2026 · NFPA 70 (NEC) Table 400.5(A)(1), ampacity of flexible cords, and Table 400.4, cord types (summarized); 29 CFR 1926.405(a)(2)(ii)(I) and (J), 1926.405(g)(2), 1926.404(b)(1), 1926.416(e) and 1910.334(a) (osha.gov); the Southwire, Coleman Cable and Woods product data on this site (gauge, length, type, amp rating, lighted end, GFCI as printed) and the Southwire published cord selection chart

Why the tool is slow at the end of the cord. Every foot of copper has resistance; a 100 foot 16 gauge cord feeding a 15 amp saw drops the voltage at the saw by more than 10 percent, so the motor draws more current to do the same work, heats, and dies young. The gauge is chosen for the amps and the length together, and the OSHA rules add the jacket type, the ground, the GFCI and the inspection. The cards go through the jacket code, the ampacity table, length, the rules, and inspection.

Extension cords, question by question

Ampacities are NEC Table 400.5(A)(1); length guidance is the makers’ charts; the rules are 1926.405, 1926.404 and 1926.416.

How do I read the letters on the jacket?The first number is the gauge (AWG; smaller number, bigger wire), the second the conductor count (12/3 is three conductors). Then the type letters: S is hard service (600 volt, thick jacket); SJ is junior hard service (300 volt, lighter jacket, the common extension cord); O means oil-resistant (SJO, SO; a second O, SJOO, means oil-resistant insulation and jacket); T means thermoplastic jacket (SJT, ST) rather than rubber; E means thermoplastic elastomer (SJEW, SEOW, the flexible cold-weather jacket); W means rated for outdoor and wet locations (SJTW, SJEOW). 1926.405(a)(2)(ii)(J) requires hard or junior hard service with a ground for tools; W for outdoors. Gauge, type and voltage are printed every few feet.
What is the ampacity by gauge?NEC Table 400.5(A)(1), column B (three current-carrying conductors): 18 AWG 7 amps, 16 AWG 10, 14 AWG 15, 12 AWG 20, 10 AWG 25, 8 AWG 35; column A (two current-carrying conductors, as in a three-wire cord where the ground carries nothing) is 18 AWG 10, 16 AWG 13, 14 AWG 18, 12 AWG 25, 10 AWG 30. The makers rate cords conservatively and print 13 amps on most 16 gauge cords and 15 on 14 and 12 gauge because the plug and receptacle are 15 amp devices; a 20 amp cord carries a 20 amp plug (T-blade). Ampacity is the heating limit; it does not account for length.
How does length change the gauge I need?Voltage drop is proportional to current times length; the NEC recommends keeping drop to 3 percent on a branch circuit and the makers build their charts on it. Typical chart: 0 to 10 amps, 16 AWG to 50 feet, 14 to 100; 10 to 15 amps, 14 AWG to 50 feet, 12 to 100; 15 to 20 amps, 12 AWG to 50 feet, 10 to 100 and beyond; 100 to 150 feet add a gauge. Motor tools (saws, compressors, grinders) draw several times their rating on start-up and suffer most from drop; heaters and lights less so. Two cords in series add their lengths. The tool nameplate gives the amps (or watts divided by 120).
What does OSHA require of the cord itself?1926.405(a)(2)(ii)(J): extension cord sets used with portable electric tools and appliances shall be of three-wire type and designed for hard or extra-hard usage (the note lists S, ST, SO, STO, SJ, SJO, SJT, SJTO); flexible cords for temporary and portable lights the same. (a)(2)(ii)(I): flexible cords and cables protected from damage, and sharp corners and projections avoided; a cord through a doorway or other pinch point only if protected. (g)(1)(iii)(B) and (C): cords not run through holes in walls, ceilings or floors, or through doorways and windows except as (a)(2)(ii)(I) allows. (g)(2)(iii): cords used only in continuous lengths without splice or tap, except that hard service cord 12 AWG or larger may be repaired if the splice retains the insulation, outer sheath and usage characteristics of the cord. (g)(2)(iv): strain relief so the cord does not pull on the plug terminals. 1910.305(g) carries the general industry equivalents, and 1910.305(g)(1)(iv) prohibits cords as a substitute for fixed wiring, through walls or attached to surfaces.
When is a GFCI required on a cord?1926.404(b)(1)(ii): all 120 volt, single-phase, 15 and 20 ampere receptacle outlets on construction sites that are not part of the permanent wiring of the building and are in use by employees have ground-fault circuit interrupters, including receptacles on extension cords connected to a generator; or (iii) the employer runs an assured equipment grounding conductor program with written procedures, continuity and polarity tests on every cord set every three months and after repair, and color-coded tape by quarter. In practice sites use GFCI-protected spider boxes, in-line GFCI cord sets or plug-in GFCI adapters at the source, and 1910.304(b)(3) brings the same to general industry temporary wiring. The GFCI guide linked below covers the program.
What does the inspection look for?1926.416(e)(1) and 1910.334(a)(2): cords and cord sets are visually inspected before use on each shift for external defects (deformed or missing pins, insulation damage, cut jacket exposing the inner insulation) and for signs of internal damage (pinched or crushed jacket); a damaged cord is removed from service until repaired and tested. Specific checks: the ground pin present and tight (a cord with the pin broken off is a violation, not a convenience); the plug and connector molded or clamped with strain relief; no tape repairs on a cord smaller than 12 AWG; the jacket not cut, cracked, burned or swollen; the W rating for outdoor use; and the lighted end or GFCI indicator working. Cords are stored coiled loosely and not pulled by the cord.
Lighted ends, locking plugs, 20 amp and 240 volt cordsA lighted connector end shows the cord is energized at the tool end. Twist-lock (NEMA L5-15, L5-20, L6-20) cords and plugs stay connected under tension on generators and lifts and match the receptacle configuration. 20 amp cords carry the NEMA 5-20 T-blade plug and 12 or 10 AWG; 240 volt cords (6-15, 6-20, 6-30, 14-50) for welders and RVs are 10 or 8 AWG with the matching plug, and a 240 volt cord is never adapted to a 120 volt tool. Cord reels are rated for the cord fully unwound; a coiled cord under load heats and the reel derating on the label applies. Triple-tap ends spread the load across three tools and the gauge still has to carry the total.
What about cords in general industry and in wet locations?1910.305(g)(1): flexible cords are not used as a substitute for fixed wiring, run through holes in walls, ceilings or floors, run through doorways or windows, attached to building surfaces, or concealed behind walls; 1910.305(g)(2): cords used only in continuous lengths without splice, with strain relief and the ground connected; 1910.304(b)(3)(ii): GFCI or the assured grounding program for temporary wiring and cord sets in maintenance and construction-like activities. Wet locations: a W-rated cord, GFCI protection, connectors kept off the ground or in a cord cover, and the 1926.405(a)(2)(ii)(E) rule that receptacles in wet locations have weatherproof covers. The electrician PPE guide covers working on energized equipment, which a cord repair is not unless it is unplugged.

In plain words

  • 12/3 SJTW: 12 gauge, three wires, junior hard service, thermoplastic, outdoor.
  • Ampacity: 16 gauge 10 to 13 amps, 14 gauge 15, 12 gauge 20, 10 gauge 25.
  • Length: 15 amps on 14 gauge to 50 feet and 12 gauge to 100; 20 amps on 12 to 50 and 10 to 100.
  • Jobsite cords: three-wire, S or SJ type, W outdoors; no splices under 12 gauge; not through doors or holes unprotected.
  • GFCI or an assured grounding program on every cord set (1926.404(b)(1)).
  • Inspect every shift: ground pin, plug, jacket; damaged cords out.

Questions people ask

What gauge extension cord for a 15 amp tool?

The makers’ charts list 14 AWG to 50 feet and 12 AWG to 100 feet; 16 AWG is for loads under 10 amps and short runs.

What does 12/3 mean on an extension cord?

12 AWG conductors, three of them: hot, neutral and ground.

Can you splice an extension cord?

Only a hard service cord 12 AWG or larger, with a repair that restores the original insulation and jacket (1926.405(g)(2)(iii)); otherwise no splices or taps.

Does OSHA require GFCI on extension cords?

On construction sites, every 120 volt 15 and 20 amp receptacle not part of permanent wiring, including cord ends, has GFCI protection or is in an assured equipment grounding program (1926.404(b)(1)).

Can a cord run through a doorway?

Only if protected from damage at the pinch point (1926.405(a)(2)(ii)(I)); never through holes in walls, floors or ceilings.

Is a cord with a broken ground pin OK to use?

No; it is a defect under 1926.416(e) and 1910.334(a) and the cord is removed until the plug is replaced.

The ratings, test results and standards shown here are the manufacturers' published values, reproduced as published. Nothing on this page is a recommendation by Bayshore Safety that any product is suitable for a particular task, hazard or workplace. Selecting safety products and protective equipment is the responsibility of the end user and the employer, based on their own hazard assessment and the regulations that apply to their work. Confirm every value on the manufacturer's own documentation before use.

Outfitting a jobsite or shop with cords, lights and batteries?Call (925) 215-7337 or email us the tools, the run lengths and the quantities and we will quote cords, GFCIs, lights and batteries by the case with the part numbers listed. We sell nationwide.
All electrical and lighting guides

© 2026 Bayshore Safety & Industrial Supplies, Inc. All rights reserved. This guide may not be copied or republished without written permission.

How to buyCard, purchase order or invoice terms; quotes on request; agencies and institutions welcome.
Live Service & SupportReal people who know the products, Monday to Friday 7:30am to 4pm Pacific. 925-215-7337
We DeliverWe ship nationwide. Parcel and LTL freight to job sites and businesses across the U.S.