When is a GFCI required on a construction site, and what is the assured equipment grounding conductor program? The two choices in 1926.404(b)(1), which receptacles are covered, generators, portable and in-line GFCIs, Class A trip levels, open-neutral protection, testing a GFCI, the AEGC written program with continuity and polarity tests and the quarterly tape colors, and the general industry rule
Since 1926.404(b)(1) took effect, every construction employer has to protect its workers from ground faults on temporary power one of two ways. (b)(1)(ii): ground-fault circuit interrupters for all 120 volt, single-phase, 15 and 20 ampere receptacle outlets on the site that are not part of the permanent wiring of the building or structure and are in use by employees, including receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated over 5 kW whose circuit conductors are insulated from the frame (smaller generators are exempt by the same paragraph); or (b)(1)(iii): an assured equipment grounding conductor program covering all cord sets, receptacles not part of the permanent wiring, and cord-and-plug equipment, with a written description at the site, a competent person to implement it, a visual inspection of every cord set and receptacle before each day’s use, and two tests on every cord set, receptacle and piece of equipment: continuity of the equipment grounding conductor and correct attachment of that conductor to its terminal, performed before first use, after any repair, after any incident that could have caused damage (a cord run over), and at intervals not exceeding three months (six months for cord sets and receptacles that are fixed and not exposed to damage), with the tests recorded by means that identify each item and the date, which is where the quarterly color-coded tape convention comes from (a common scheme: white for January to March, green April to June, red July to September, orange October to December, with brown for a repaired item). Most employers choose GFCIs, because the device does the protecting: a Class A GFCI trips when the current leaving on the hot differs from the current returning on the neutral by 4 to 6 milliamps, within about 25 milliseconds, which is below the level that stops a heart; it does not need a ground to work, which is why it protects even a two-wire tool, and it does not protect against a hot-to-neutral shock or overload (the breaker does that). Portable GFCIs come as in-line cord sets, plug-in adapters, quad boxes and spider boxes, in manual-reset (open-neutral protected, will not come back on by itself after a power loss, the type OSHA letters and the makers call for on construction) and automatic-reset (for refrigerators and pumps that must restart); every GFCI is tested with its own test button before each use and monthly at least, and a GFCI that will not trip or reset is replaced. 1910.304(b)(3)(ii) brings the same requirement to general industry for temporary wiring and cord sets used in construction-like work, maintenance, remodeling and repair, and 1926.404(b)(1)(i) requires the employer to use one method or the other on top of all other grounding rules. The band lists the portable GFCIs, GFCI cord sets, receptacle testers, tape and cords we stock.
Why the GFCI replaced a clipboard. Before 1976 the only protection on a jobsite cord was the ground wire, and a ground wire broken inside a cord or a two-prong tool gave none. The standard lets the employer keep testing every ground every quarter and writing it down, or put a device on the line that trips before a shock becomes lethal. The device wins on nearly every site, and the paperwork program survives where GFCIs nuisance-trip on long runs and wet equipment. The cards cover both, the device itself, generators, and testing.
GFCIs and the AEGC program, question by question
The two options are 1926.404(b)(1)(ii) and (iii); device behavior is UL 943 and the makers’ data.
In plain words
- Every temporary 120 volt, 15 or 20 amp outlet a worker uses on a site is on a GFCI, or the employer runs the written assured grounding program.
- A Class A GFCI trips at 4 to 6 mA with or without a ground; it does not stop hot-to-neutral shocks or overloads.
- Manual-reset, open-neutral GFCIs at the source: in-line cords, adapters, spider boxes; automatic reset is for appliances, not tools.
- Generators over 5 kW with insulated conductors are covered; most now ship with GFCIs.
- Test with the button before use; a GFCI that will not trip or reset is replaced.
- AEGC: written program, competent person, daily look, continuity and polarity tests at least quarterly, recorded (the tape colors).
Questions people ask
Does OSHA require GFCIs on construction sites?
Yes, on all temporary 120 volt 15 and 20 amp receptacles in use by employees, unless the employer runs an assured equipment grounding conductor program (1926.404(b)(1)).
What is the assured equipment grounding conductor program?
A written program with daily visual inspection and quarterly continuity and polarity tests of every cord set, receptacle and cord-and-plug tool, recorded by item and date (1926.404(b)(1)(iii)).
What do the colored tapes on extension cords mean?
The quarter the cord was last tested under the AEGC program; the common scheme is white, green, red, orange by quarter and brown for a repair.
At what current does a GFCI trip?
A Class A GFCI trips between 4 and 6 milliamps of imbalance (UL 943).
Does a GFCI work without a ground wire?
Yes; it compares hot and neutral current and needs no ground to detect a fault.
Should jobsite GFCIs be manual or automatic reset?
Manual reset with open-neutral protection for tools and cord sets; automatic reset is for appliances that must restart on their own.
Related guides
Extension cord gauge, length and amperageThe cords the GFCI protectsWhat PPE should an electrician wear?Energized work and 70EOSHA Focus Four hazardsElectrocution in constructionElectrical panel labelingMarking the temporary panelCompetent person vs qualified personWho runs the AEGC programThe ratings, test results and standards shown here are the manufacturers' published values, reproduced as published. Nothing on this page is a recommendation by Bayshore Safety that any product is suitable for a particular task, hazard or workplace. Selecting safety products and protective equipment is the responsibility of the end user and the employer, based on their own hazard assessment and the regulations that apply to their work. Confirm every value on the manufacturer's own documentation before use.