Guide · Electrical and lighting · 1926.404(b)(1), portable GFCIs, the AEGC program and quarterly color codes

Bayshore Safety & Industrial Supplies Guide

When is a GFCI required on a construction site, and what is the assured equipment grounding conductor program? The two choices in 1926.404(b)(1), which receptacles are covered, generators, portable and in-line GFCIs, Class A trip levels, open-neutral protection, testing a GFCI, the AEGC written program with continuity and polarity tests and the quarterly tape colors, and the general industry rule

Since 1926.404(b)(1) took effect, every construction employer has to protect its workers from ground faults on temporary power one of two ways. (b)(1)(ii): ground-fault circuit interrupters for all 120 volt, single-phase, 15 and 20 ampere receptacle outlets on the site that are not part of the permanent wiring of the building or structure and are in use by employees, including receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated over 5 kW whose circuit conductors are insulated from the frame (smaller generators are exempt by the same paragraph); or (b)(1)(iii): an assured equipment grounding conductor program covering all cord sets, receptacles not part of the permanent wiring, and cord-and-plug equipment, with a written description at the site, a competent person to implement it, a visual inspection of every cord set and receptacle before each day’s use, and two tests on every cord set, receptacle and piece of equipment: continuity of the equipment grounding conductor and correct attachment of that conductor to its terminal, performed before first use, after any repair, after any incident that could have caused damage (a cord run over), and at intervals not exceeding three months (six months for cord sets and receptacles that are fixed and not exposed to damage), with the tests recorded by means that identify each item and the date, which is where the quarterly color-coded tape convention comes from (a common scheme: white for January to March, green April to June, red July to September, orange October to December, with brown for a repaired item). Most employers choose GFCIs, because the device does the protecting: a Class A GFCI trips when the current leaving on the hot differs from the current returning on the neutral by 4 to 6 milliamps, within about 25 milliseconds, which is below the level that stops a heart; it does not need a ground to work, which is why it protects even a two-wire tool, and it does not protect against a hot-to-neutral shock or overload (the breaker does that). Portable GFCIs come as in-line cord sets, plug-in adapters, quad boxes and spider boxes, in manual-reset (open-neutral protected, will not come back on by itself after a power loss, the type OSHA letters and the makers call for on construction) and automatic-reset (for refrigerators and pumps that must restart); every GFCI is tested with its own test button before each use and monthly at least, and a GFCI that will not trip or reset is replaced. 1910.304(b)(3)(ii) brings the same requirement to general industry for temporary wiring and cord sets used in construction-like work, maintenance, remodeling and repair, and 1926.404(b)(1)(i) requires the employer to use one method or the other on top of all other grounding rules. The band lists the portable GFCIs, GFCI cord sets, receptacle testers, tape and cords we stock.

Bayshore Safety. Industrial safety and PPE supplier since 2017. · Current as of November 2026 · 29 CFR 1926.404(b)(1)(i) to (iii), Ground-fault protection (osha.gov); 29 CFR 1910.304(b)(3) (general industry ground-fault protection for temporary wiring) and 1926.416(e); OSHA Publication 3007, Ground-Fault Protection on Construction Sites, and OSHA letters of interpretation on generators and automatic-reset GFCIs; UL 943, Ground-Fault Circuit-Interrupters (Class A trip thresholds; summarized); the Southwire, Tower, Ericson and Klein product data on this site (GFCI type, reset type, amperage, tester functions as printed)

Why the GFCI replaced a clipboard. Before 1976 the only protection on a jobsite cord was the ground wire, and a ground wire broken inside a cord or a two-prong tool gave none. The standard lets the employer keep testing every ground every quarter and writing it down, or put a device on the line that trips before a shock becomes lethal. The device wins on nearly every site, and the paperwork program survives where GFCIs nuisance-trip on long runs and wet equipment. The cards cover both, the device itself, generators, and testing.

GFCIs and the AEGC program, question by question

The two options are 1926.404(b)(1)(ii) and (iii); device behavior is UL 943 and the makers’ data.

Which receptacles does 1926.404(b)(1)(ii) cover?All 120 volt, single-phase, 15 and 20 ampere receptacle outlets on construction sites which are not a part of the permanent wiring of the building or structure and which are in use by employees. That is every temporary power pole, spider box, generator outlet (over 5 kW, insulated from frame) and extension cord end an employee plugs a tool into. Receptacles that are part of the permanent wiring (the building’s own outlets once energized) are not covered by this paragraph but are covered by the NEC’s own GFCI requirements in many locations and by the employer’s hazard assessment. 240 volt and three-phase circuits are not in the GFCI paragraph and fall under the AEGC program or other protection.
What is a Class A GFCI, and what does it not do?UL 943: a Class A GFCI trips when the difference between the current on the ungrounded (hot) and grounded (neutral) conductors reaches 6 mA (and does not trip below 4 mA), in a time that shortens as the fault grows (about 25 ms at a hard fault). The imbalance means current is leaving the circuit through something else, usually a person; the device opens before the current reaches the level that causes ventricular fibrillation. It works with no ground present. It does not trip on a shock between hot and neutral where the current returns on the neutral (holding both wires), does not protect against overload or short circuit (the breaker does), and does not trip for a fault on the line side of it. A GFCI on the cord protects only what is downstream of it, which is why it goes at the source.
Portable, in-line, plug-in or spider box?In-line GFCI cord sets (a GFCI molded into a 2 to 50 foot cord, often with a triple tap) protect everything downstream and are the simplest way to meet (b)(1)(ii) at a generator or a permanent outlet; plug-in GFCI adapters (single and triple outlet) do the same in a smaller package; quad boxes and spider boxes (temporary power distribution with GFCI-protected 20 amp receptacles and a 50 amp inlet) feed a crew from one drop; GFCI receptacles in a temporary panel protect that circuit. All of them are rated 15 or 20 amps at 120 volts, carry an open-neutral feature (the device trips if the neutral is lost so it fails safe), and are marked UL 943 Class A. Manual reset is the construction type: after a trip or a power interruption it stays off until someone pushes reset, so a tool does not restart unattended; automatic reset is for freezers and sump pumps and OSHA’s letters say it is not for cord sets feeding tools.
What about generators?1926.404(b)(1)(ii) covers receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated more than 5 kW where the circuit conductors are insulated from the generator frame and all other grounded surfaces; smaller generators are exempt from the GFCI paragraph, though the employer may still use GFCIs and the generator maker usually builds them in. 1926.404(f)(3) covers grounding the generator frame (a portable generator supplying only cord-and-plug equipment through its own receptacles need not have its frame grounded to a rod if the frame is bonded to the receptacle grounding terminals and the fuel tank is bonded). Modern generators ship with GFCI receptacles; an older one is fed through an in-line GFCI cord. Bonded neutral versus floating neutral determines whether a plug-in GFCI will hold on a given generator, and the makers’ notes say so.
How is a GFCI tested?With its own test button before each use (and monthly at least on fixed units): pressing test creates a fault on the device’s own circuit and it must trip; pressing reset must restore power. A plug-in receptacle tester with a GFCI test button checks a receptacle for wiring (open ground, reversed polarity, open neutral) and then trips the GFCI protecting it, and is the quick check at a spider box; a tester cannot test a GFCI’s trip level, which is done with a GFCI tester that applies 6 mA and times the trip. A GFCI that does not trip on test, does not reset, trips repeatedly on a dry cord with a known-good tool, or is cracked or wet inside is replaced. 1926.416(e) and 1910.334 cover the daily visual inspection of the cord and device.
What does the assured equipment grounding conductor program require?1926.404(b)(1)(iii): (A) a written description of the program, including the specific procedures, available at the jobsite for inspection by OSHA and any affected employee; (B) one or more competent persons designated to implement it; (C) each cord set, attachment cap, plug and receptacle of cord sets, and any equipment connected by cord and plug, except those that are fixed and not exposed to damage, visually inspected before each day’s use for external defects and internal damage, with damaged equipment not used until repaired; (D) two tests on all cord sets, receptacles not part of the permanent wiring, and cord-and-plug equipment required to be grounded: continuity of the equipment grounding conductor, and that it is connected to its proper terminal; (E) tests performed before first use, before equipment is returned to service after repairs, before it is returned after any incident that can reasonably be suspected to have caused damage, and at intervals not to exceed 3 months (6 months for cord sets and receptacles that are fixed and not exposed to damage); (F) the employer does not make available or permit use of equipment that has not met these requirements; (G) tests recorded, identifying each receptacle, cord set and item of equipment that passed and the last date it was tested or the interval, kept until replaced by a more current record and made available on the site. The record is usually a color-coded tape at the plug end plus a log.
What are the quarterly tape colors?The standard does not name colors; it requires a record identifying each item and its test date or interval. The convention most contractors use (and many write into their program): white for the first quarter (January to March), green for the second (April to June), red for the third (July to September), orange for the fourth (October to December), with brown added when an item is repaired and retested between quarters, and the previous quarter’s tape removed when the new one goes on. The written program states the scheme in use, and a cord without current tape is not used under (b)(1)(iii)(F). Many sites run GFCIs and the program together so a nuisance-tripping GFCI can be bypassed for the day without losing compliance.
What does general industry require?1910.304(b)(3)(ii): ground-fault protection for employees during construction-like activities (maintenance, remodeling, repair of buildings, structures or equipment, and similar activities) for 125 volt, 15, 20 and 30 ampere receptacles not part of the permanent wiring, with the same GFCI-or-AEGC choice, and (b)(3)(iii) for the AEGC program details; 1910.304(b)(3)(i) adds GFCI protection for receptacles in bathrooms and on rooftops. Outside those activities, general industry plants rely on the NEC’s GFCI locations, the equipment grounding rules of 1910.304(g), and the cord inspection of 1910.334(a). The extension cord guide covers the cord side of all of this.

In plain words

  • Every temporary 120 volt, 15 or 20 amp outlet a worker uses on a site is on a GFCI, or the employer runs the written assured grounding program.
  • A Class A GFCI trips at 4 to 6 mA with or without a ground; it does not stop hot-to-neutral shocks or overloads.
  • Manual-reset, open-neutral GFCIs at the source: in-line cords, adapters, spider boxes; automatic reset is for appliances, not tools.
  • Generators over 5 kW with insulated conductors are covered; most now ship with GFCIs.
  • Test with the button before use; a GFCI that will not trip or reset is replaced.
  • AEGC: written program, competent person, daily look, continuity and polarity tests at least quarterly, recorded (the tape colors).

Questions people ask

Does OSHA require GFCIs on construction sites?

Yes, on all temporary 120 volt 15 and 20 amp receptacles in use by employees, unless the employer runs an assured equipment grounding conductor program (1926.404(b)(1)).

What is the assured equipment grounding conductor program?

A written program with daily visual inspection and quarterly continuity and polarity tests of every cord set, receptacle and cord-and-plug tool, recorded by item and date (1926.404(b)(1)(iii)).

What do the colored tapes on extension cords mean?

The quarter the cord was last tested under the AEGC program; the common scheme is white, green, red, orange by quarter and brown for a repair.

At what current does a GFCI trip?

A Class A GFCI trips between 4 and 6 milliamps of imbalance (UL 943).

Does a GFCI work without a ground wire?

Yes; it compares hot and neutral current and needs no ground to detect a fault.

Should jobsite GFCIs be manual or automatic reset?

Manual reset with open-neutral protection for tools and cord sets; automatic reset is for appliances that must restart on their own.

The ratings, test results and standards shown here are the manufacturers' published values, reproduced as published. Nothing on this page is a recommendation by Bayshore Safety that any product is suitable for a particular task, hazard or workplace. Selecting safety products and protective equipment is the responsibility of the end user and the employer, based on their own hazard assessment and the regulations that apply to their work. Confirm every value on the manufacturer's own documentation before use.

Outfitting a jobsite or shop with cords, lights and batteries?Call (925) 215-7337 or email us the tools, the run lengths and the quantities and we will quote cords, GFCIs, lights and batteries by the case with the part numbers listed. We sell nationwide.
All electrical and lighting guides

© 2026 Bayshore Safety & Industrial Supplies, Inc. All rights reserved. This guide may not be copied or republished without written permission.

How to buyCard, purchase order or invoice terms; quotes on request; agencies and institutions welcome.
Live Service & SupportReal people who know the products, Monday to Friday 7:30am to 4pm Pacific. 925-215-7337
We DeliverWe ship nationwide. Parcel and LTL freight to job sites and businesses across the U.S.