Bayshore Safety & Industrial Supplies Guide
Oxygen and acetylene cylinder storage: the 20 foot rule, caps, carts, chains and the 15 psig acetylene limit? What 1910.253(b) and 1926.350 require for storing, securing and moving cylinders, keeping oil off oxygen equipment, cylinder carts and the regulator-off rule, acetylene upright time, and marking empties
The cylinder rules for welding gases are in 29 CFR 1910.253(b) (general industry) and 1926.350(a) (construction), and they repeat each other on the points inspectors look for. Storage: oxygen cylinders in storage are separated from fuel-gas cylinders and from combustible materials (oil, grease, acetylene) by at least 20 feet, or by a noncombustible barrier at least 5 feet high with a half-hour fire rating (1910.253(b)(4)(iii), 1926.350(a)(10)); cylinders are kept away from heat, out of unventilated lockers and cupboards, and away from elevators, stairs and gangways where they can be knocked over (1910.253(b)(2)). Securing: construction requires cylinders secured upright at all times except briefly while being hoisted or carried (1926.350(a)(9)); general industry requires fuel-gas cylinders valve end up in use and the makers and CGA P-1 require all cylinders chained or strapped so they cannot fall. Caps: valve protection caps hand-tight and in place whenever the cylinder is not connected for use (1910.253(b)(2)(iv)). Moving: valves closed, regulators removed unless the cylinders are on a cart built to carry them with regulators attached, no slings, magnets or hooks on the cap, never rolled on the ground on the side, never dropped (1910.253(b)(5)(ii)). Oxygen: no oil or grease on cylinders, valves, regulators, hose or hands (1910.253(b)(5)(i)); oxygen is never used as compressed air. Acetylene: never used at more than 15 psig (1910.253(a)(2)), stored and used valve up, and a cylinder that has been on its side is stood up and left before use per the gas supplier’s instruction (commonly the same time it lay down, up to a day). Empties are marked, valves closed, caps on, stored apart from full cylinders. The band lists the cylinder carts, caps, chains, cylinder wrenches and storage we stock.
Why the cylinder rules are about falling over and about oil. A full oxygen cylinder weighs about 150 lb at 2,200 psi; knock the valve off and it is a projectile. Oil or grease in an oxygen regulator can ignite at the pressure of the cylinder. Acetylene above 15 psig can decompose by itself. Everything in 1910.253(b) traces to one of those three facts: keep cylinders upright and capped, keep oil away from oxygen, keep acetylene at low pressure and valve up. The cards take the paragraphs in the order they are cited.
Cylinder rules, question by question
Paragraph numbers are 1910.253 unless the construction rule 1926.350 is named; CGA P-1 is the supplier practice behind them.
In plain words
- Stored oxygen and acetylene: 20 feet apart or a 5 foot half-hour wall between them.
- Upright and chained, caps hand-tight whenever the regulator is off, away from heat and traffic.
- Move them capped on a cart; never by the cap, never dropped, never rolled on the side.
- No oil or grease anywhere near oxygen; oxygen is not compressed air.
- Acetylene never above 15 psig, always valve up, stood up and rested if it was on its side.
- Empties marked, capped and kept apart; leakers go outside and the supplier is called.
Questions people ask
How far apart do oxygen and acetylene cylinders have to be stored?
20 feet, or separated by a noncombustible barrier at least 5 feet high with a half-hour fire rating (1910.253(b)(4)(iii)).
Do gas cylinders have to be chained?
Construction requires them secured upright at all times (1926.350(a)(9)); CGA P-1 and the suppliers require it everywhere.
When do cylinder caps have to be on?
Whenever the cylinder is not connected for use: storage, transport and any time the regulator is off (1910.253(b)(2)(iv)).
Why can acetylene not exceed 15 psi?
Above 15 psig acetylene can decompose explosively on its own (1910.253(a)(2)).
How long should an acetylene cylinder stand up after lying down?
The suppliers state the time; the common instruction is at least as long as it lay down, up to 24 hours, before use.
Can you move a cylinder with the regulator on?
Only on a cart built to carry cylinders with regulators attached; otherwise the regulator comes off and the cap goes on (1910.253(b)(5)(ii)(D)).
Related guides
Oxy-fuel regulators, CGA connections and flashback arrestorsWhat fits which cylinderHand trucks, dollies and cylinder cartsCart capacitiesHow to store compressed gas cylinders and calibration gasThe general compressed gas rule and calibration cylindersHot work permits1910.252(a) and the fire watchOxy-fuel cutting tip sizes, gases and pressuresThe torch end of the systemWelding blankets, curtains and screensProtecting what is around the workThe ratings, test results and standards shown here are the manufacturers' published values, reproduced as published. Nothing on this page is a recommendation by Bayshore Safety that any product is suitable for a particular task, hazard or workplace. Selecting safety products and protective equipment is the responsibility of the end user and the employer, based on their own hazard assessment and the regulations that apply to their work. Confirm every value on the manufacturer's own documentation before use.