Guide · Data centers · NFPA 10 (2026)

Which fire extinguisher does a data center need? What NFPA 10 (2026) says about clean agent extinguishers for data halls, server rooms and electrical rooms

NFPA 10 (2026) answers it in two sections. 5.5.4.6.1: extinguishers protecting delicate electronic equipment are selected from types listed and labeled for Class C. 5.5.4.6.2: dry chemical extinguishers are not installed for that protection. That leaves the Class C-listed clean agents: halocarbon units such as Halotron BrX and Halotron I, carbon dioxide, and water mist. Sizing comes from 6.4.3, which treats the electrical fire as the Class A or Class B fire underneath it: a 2A:10B:C unit meets the light and ordinary Class A minimum within 75 ft of travel (Table 6.2.1.1) and the light Class B minimum within 30 ft (Table 6.3.1.1). Placement of any halogenated unit must respect the nameplate minimum room volume (5.3.2.6.1), which is why small battery rooms and IDF closets get the 3.75 lb units and data halls get the 12.5 lb 551. NFPA 75 is on the list of occupancy standards to read alongside (5.5.5.1); NFPA 10 remains the floor (5.5.5.2).

Bayshore Safety. Industrial safety and PPE supplier since 2017. · Current as of November 2026 · NFPA 10 (2026) 5.3.2.6.1, 5.5.4.6, 5.5.5, 6.2, 6.3, 6.4, 7.3.6.3; Amerex HT Series sheet; Amerex data center brochure
Amerex 28084 Model 551 Halotron BrX Clean Agent Fire Extinguisher, 12.5 lbAmerex 28084 Model 551 Halotron BrX Clean Agent Fire Extinguisher, 12.5 lbHalotron BrX, 2A:10B:C, listed for rooms of 2,988 cu ft and up

Why is the room volume the number that catches projects? A halogenated agent in a small closed room can reach a concentration the label does not allow, so UL 2129 listings carry a minimum room volume and NFPA 10 5.3.2.6.1 makes placement follow it. On a hyperscale build the data halls are tens of thousands of cubic feet and the 551 fits everywhere; the battery rooms and IDF closets may be 2,000 cubic feet or less, below the 551's 2,988, and need the 547 or 549 (896) instead. Measure every room type before the submittal.

A data-center extinguisher package, room by room

The same four units cover every room type; the room volume picks which.

Data hall551 (2A:10B:C): Class C listed, meets the Class A and light Class B minimums, 2,988 cu ft minimum room. Within 75 ft of travel from any point (6.2.1.2.2).
Electrical and switchgear rooms551 where the room is 2,988 cu ft or more; 549 or 547 (5B:C) where it is 896 to 2,987 (5.3.2.6.1). Class C required (6.4.1).
UPS and battery roomsUsually small: 549 or 547 from 896 cu ft, A537TS from 427. NFPA 10 has no class for lithium-ion batteries and these units are not listed for them; NFPA 855 governs energy storage.
MDF, IDF and telecom closetsA537TS (2B:C) from 427 cu ft, 547 or 549 from 896. NFPA 76 is the telecom occupancy standard to read with NFPA 10 (5.5.5.1).
Everywhere elseABC dry chemical building protection (5.5.2) where no delicate electronics are being protected; 2-A within 75 ft.
Cabinets and mountingHanger or manufacturer bracket, never field-made (6.1.3.4); top of a unit under 40 lb no more than 5 ft up (6.1.3.9); surface-mounted or listed fire-rated cabinets on fire-rated walls (6.1.3.11.6).
NFPA 10 (2026) sections a data-center submittal cites
SectionIn plain wordsWhy it matters to the package
5.5.4.6.1Delicate electronic equipment: Class C-listed typesRules in clean agent, CO2, water mist
5.5.4.6.2No dry chemical for that protectionRules out ABC in the data hall
5.3.2.6.1Halogenated agents follow the nameplate minimum room volumePicks the model per room
6.4.3Class C units sized on the Class A or B hazard2A:10B:C meets the hall; 5B:C the small rooms where the A is met elsewhere
Table 6.2.1.12-A minimum, 75 ft travel, 11,250 sq ft per unitUnit count per floor
Table 6.3.1.15-B at 30 ft or 10-B at 50 ft (light hazard)Travel distance in halls with Class B
7.3.6.3Nonrechargeable: no 6-year or hydro; 12-year replacementMaintenance cost line in the owner handover
5.5.5.1 / 5.5.5.2Review NFPA 75 and 76; NFPA 10 is the minimumSpec cross-references

Source: NFPA 10 (2026), sections as cited; read on NFPA's free access. Summaries are ours.

Class C-listed clean agent units for data centers

9 items · prices live

Each unit lists its rating and part number; the minimum room volume is on the product page. Prices are live.

ItemRatingPart numberPrice
Amerex 28084 Model 551 Halotron BrX Clean Agent Fire Extinguisher, 12.5 lb
Rating2A:10B:CPart28084
$1,431.84

ItemRatingPart numberPrice
Amerex 15510 Model 398 Halotron I Clean Agent Fire Extinguisher, 15.5 lb
Rating2A:10B:CPart15510
$2,256.25
Amerex 15509 Model 397 Halotron I Clean Agent Fire Extinguisher, 11 lb
Rating1A:10B:CPart15509
$1,570.75

ItemRatingPart numberPrice
Amerex 01714 Model 330 Carbon Dioxide Fire Extinguisher, 10-B:C, 10 lb
Rating10-B:CPart01714
$459.95
Amerex 01708 Model 332 Carbon Dioxide Fire Extinguisher, 10-B:C, 20 lb
Rating10-B:CPart01708
$686.96
Amerex 27702 Model C272 Water Mist Fire Extinguisher, 2-A:C, 2.5 Gallon
Rating2-A:CPart27702
$344.59

Cabinets, brackets and signs are in Fire protection accessories.

Questions people ask

What fire extinguisher does NFPA 10 require in a data center?

A type listed and labeled for Class C where delicate electronic equipment is protected, and not dry chemical (NFPA 10 (2026) 5.5.4.6.1, 5.5.4.6.2).

Can an ABC extinguisher be used in a server room?

5.5.4.6.2 says dry chemical is not installed to protect delicate electronic equipment. ABC units may still serve as building protection elsewhere (5.5.2).

How many extinguishers does a data hall need?

Class A: one per 11,250 sq ft minimum and within 75 ft of travel from any point (Table 6.2.1.1, 6.2.1.2); Class C units are counted on that basis (6.4.3).

What is the minimum room size for a Halotron BrX extinguisher?

On Amerex's data: 551, 2,988 cu ft; 547 and 549, 896; A537TS, 427. NFPA 10 (2026) 5.3.2.6.1 requires placement to follow the nameplate.

Does NFPA 75 require fire extinguishers?

NFPA 10 lists NFPA 75 among the occupancy documents to review (5.5.5.1); read the current NFPA 75 for its own provisions. NFPA 10 remains the minimum (5.5.5.2).

Is there a clean agent extinguisher for lithium-ion batteries?

NFPA 10 (2026) has no class for lithium-ion fires and the units on this page are not listed for them; NFPA 855 covers energy storage systems.

The ratings, test results and standards shown here are the manufacturers' published values, reproduced as published. Nothing on this page is a recommendation by Bayshore Safety that any product is suitable for a particular task, hazard or workplace. Selecting safety products and protective equipment is the responsibility of the end user and the employer, based on their own hazard assessment and the regulations that apply to their work. Confirm every value on the manufacturer's own documentation before use.

Specifying clean agent extinguishers for a project?Call (925) 215-7337 or email us with the room sizes and the spec section. We sell nationwide.
Clean agent fire extinguishers
How to buyCard, purchase order or invoice terms; quotes on request; agencies and institutions welcome.
Live Service & SupportReal people who know the products, Monday to Friday 7:30am to 4pm Pacific. 925-215-7337
We DeliverWe ship nationwide. Parcel and LTL freight to job sites and businesses across the U.S.