Skip to main content
Home › Guides › Material handling and rigging › Safety cans
Guide · Material handling and rigging · Type I and Type II safety cans, 1926.152, 1910.106, NFPA 30 and flammable storage cabinets

Bayshore Safety & Industrial Supplies Guide

Type I vs Type II safety cans, and what OSHA says about gasoline containers on a jobsite? The 5 gallon rule in 1926.152(a)(1), the safety can definition in 1910.106(a)(29), flash arresters, spring-closing lids and pressure relief, one spout vs two, FM and UL listings, color coding by fuel, plastic vs steel, the 25 gallon cabinet threshold and 60 gallon cabinets, bonding and grounding, and the dispensing rules

On a construction site, 1926.152(a)(1) says only approved containers and portable tanks are used for storing and handling flammable liquids, and approved safety cans or DOT-approved containers are used for handling and use of flammable liquids in quantities of 5 gallons or less (with an exception for highly viscid materials); general industry’s 1910.106 defines the safety can in (a)(29) as an approved container of not more than 5 gallons capacity, with a spring-closing lid and spout cover, designed so it safely relieves internal pressure when exposed to fire, and limits the quantities kept outside a storage cabinet or room in (d) and (e). A Type I safety can has one opening used for both filling and pouring, with a spring-closing lid, a flame arrester screen in the spout, and a lid that vents at 3 to 5 psi; a Type II can has two openings, a fill opening with its own spring lid and a pour spout with a flexible hose and flame arrester, so it pours without removing the lid and vents through the fill cap, which is the can the makers list for dispensing into equipment and fueling. Both are listed by FM or UL (the approval the OSHA rules refer to) and the makers color them by convention: red for gasoline, yellow for diesel, blue for kerosene, green for oils, with the contents labeled under 1910.1200. Steel cans are the standard and are grounded and bonded for dispensing; polyethylene safety cans are listed, do not rust or dent, and are used where corrosive liquids or weight matter, with the maker’s note on static. 1910.106(e)(2)(ii)(b) and (d)(3) and NFPA 30 cap the flammable liquid kept outside an approved cabinet or storage room (25 gallons of Category 1 flammables in a fire area outside cabinets, or 120 gallons of Category 2 to 4, under 1910.106(e)(2)(ii)(b)), with a listed cabinet holding up to 60 gallons of Category 1, 2 or 3 and 120 of Category 4, no more than three cabinets per fire area, and the cabinet marked Flammable, Keep Fire Away; 1926.152(b) sets similar construction limits (25 gallons outside a cabinet, 60 gallons per cabinet). Dispensing: containers bonded to the receiving vessel and grounded when transferring Category 1 and 2 liquids (1910.106(e)(6)(ii)), no smoking or ignition sources within the area, and portable fuel cans not filled in a vehicle bed or on a plastic liner because of static. The band lists the Type I and Type II safety cans, funnels, faucets, plunger cans, oily waste cans and cabinets we stock.

Bayshore Safety. Industrial safety and PPE supplier since 2017. · Current as of November 2026 · 29 CFR 1926.152(a) and (b), Flammable liquids (osha.gov); 29 CFR 1910.106(a)(29), (d), (e)(2) and (e)(6), Flammable liquids (osha.gov); NFPA 30, Flammable and Combustible Liquids Code, chapters 9 and 18 (containers, cabinets, incidental use; summarized); FM 6051/6052 and UL 30 (safety can listing standards; summarized); the Justrite and Eagle product data on this site (type, capacity, material, listing, color and spout as printed)

Why the plastic jug from the gas station is not a safety can. A consumer gas can is a DOT-approved container for carrying fuel in a vehicle; a safety can is a listed container that closes itself, keeps a flame from traveling into the can, and vents before it bursts in a fire. The construction standard allows either for carrying but the makers, the insurers and most sites require the safety can for use and storage, and the general industry quantity limits are written around it. The cards cover the two OSHA definitions, Type I versus Type II, the listing and color, steel versus plastic, cabinets and quantities, and dispensing.

Safety cans and flammable storage, question by question

Text is 1926.152 and 1910.106 with NFPA 30 where OSHA adopts it; construction features are FM/UL and the makers’.

What does 1926.152(a)(1) require?Only approved containers and portable tanks for storage and handling of flammable liquids; approved safety cans or DOT-approved containers for the handling and use of flammable liquids in quantities of 5 gallons or less, except for highly viscid materials that may be in their original shipping containers; and flammable liquids not stored in areas used for exits, stairways or passage ((a)(2)). Approved means listed by a nationally recognized testing laboratory (FM or UL). A DOT container (the consumer gas can) meets the carrying part; a safety can meets it and the storage and use rules that follow.
What makes a can a safety can under 1910.106(a)(29)?An approved container of not more than 5 gallons capacity, having a spring-closing lid and spout cover and so designed that it will safely relieve internal pressure when subjected to fire exposure. In practice (FM 6051 and UL 30): a self-closing lid that cannot be left open, a flame arrester (a wire mesh screen or perforated baffle in the spout) that stops an external flame from igniting the vapor inside, a pressure relief that vents between 3 and 5 psi, and a body that will not rupture; a rugged handle and a positive lid.
Type I or Type II?Type I: one opening for filling and pouring, under one spring-closing lid; a flame arrester in that opening; the simplest and the can for storing and carrying and for pouring into open vessels. Type II: two openings, a fill opening with its own lid and a separate pour spout with a flexible metal hose and a flame arrester; pouring is controlled and the fill lid vents, so no vapor and liquid fight at the same opening; the can the makers list for fueling equipment, small engines and filling tanks with narrow necks, and for solvent dispensing. Type II D.O.T. cans add a DOT-compliant design for transport. Both come in 1 to 5 gallons (2 and 5 common); a safety can is never more than 5 gallons.
What do the colors mean, and what about labeling?Industry convention from the makers (not an OSHA rule): red for gasoline and other Category 1 flammables, yellow for diesel, blue for kerosene, green for oil and combustibles, with stainless and galvanized cans unpainted. Whatever the color, 1910.1200(f) requires the container labeled with the product identity and hazard warnings when it is a workplace container not used immediately by the person who filled it; most sites label every can with the contents. Mixing fuels in one can is not done because of residue and misidentification.
Steel or polyethylene?Steel (terne-plated or powder-coated, 24 gauge): the standard, grounded and bonded easily, conducts static away, dents and can rust at the seams; galvanized and stainless for corrosives. Polyethylene (HDPE) safety cans: listed by FM, do not rust or dent, lighter, see-through on some models, for acids, solvents and marine use; the makers note that plastic does not dissipate static and that bonding is done through the metal spout or a bonding tab and the receiving vessel is grounded. Both types have the same lid, arrester and relief features.
How much flammable liquid may be kept out of a cabinet?1910.106(e)(2)(ii)(b): in an industrial plant, the quantity of flammable liquid kept outside an inside storage room or storage cabinet in a building or any one fire area is not to exceed 25 gallons of Category 1 flammable liquids in containers, 120 gallons of Category 2, 3 or 4 liquids in containers, and 660 gallons in a single portable tank. 1926.152(b)(1): on a construction site, no more than 25 gallons of flammable liquids stored in a room outside an approved storage cabinet. Storage cabinets: not more than 60 gallons of Category 1, 2 or 3 liquids or 120 gallons of Category 4 per cabinet (1910.106(d)(3)(i)), built and vented as (d)(3)(ii) and NFPA 30 describe, marked Flammable, Keep Fire Away, and not more than three cabinets in a fire area (1926.152(b)(2) and (3) carry the same). Quantities in use at a workstation for the day are the incidental-use rules of 1910.106(e)(2).
What are the dispensing and bonding rules?1910.106(e)(6)(ii): Category 1 or 2 flammable liquids are not dispensed into containers unless the nozzle and container are electrically interconnected (bonded) and, in practice, the system is grounded; the bond is a clip and cable from the dispensing can or drum to the receiving can or vessel. (e)(6)(i) requires adequate precautions against ignition: no smoking, open flames or sparks, and ventilation. Gasoline is not pumped or poured in a truck bed liner or on a plastic surface because the can is insulated from ground; the can goes on the ground. Transfer from drums uses a listed self-closing faucet with a flame arrester, a drum vent and a bonding wire; plunger cans and bench cans dispense solvent at the bench with the same arrester and self-closing features.
What about oily waste and used solvent?Oily waste cans (foot-pedal, self-closing lid, elevated bottom) hold solvent- and oil-soaked rags so spontaneous ignition is contained; 1910.106(e)(9)(iii) and 1926.252(e) require combustible waste and oily rags kept in covered metal receptacles and removed daily (the shop towel guide covers them). Used solvent goes back into a safety can labeled as waste or a listed waste can, and disposal follows the hazardous waste rules. Safety cans are inspected for a lid that does not close, a missing arrester screen, a leaking seam or a stuck relief, and are replaced, not repaired, when the listing features fail.

In plain words

  • Five gallons or less on a jobsite goes in a safety can or a DOT container; storage and use follow the safety can rules.
  • A safety can closes itself, has a flame arrester in the spout, and vents at 3 to 5 psi before it bursts.
  • Type I: one opening, for storing and pouring into open vessels. Type II: fill lid plus a hose spout, for fueling and dispensing.
  • Red gasoline, yellow diesel, blue kerosene, green oil; label the contents either way.
  • 25 gallons of Category 1 outside a cabinet per fire area; 60 gallons per listed cabinet; three cabinets per area.
  • Bond and ground when dispensing; can on the ground, never in a bed liner; rags in a covered metal can.

Questions people ask

What is the difference between a Type I and Type II safety can?

Type I has one opening for filling and pouring; Type II has a fill opening and a separate hose spout for controlled pouring and fueling.

Does OSHA require safety cans for gasoline?

Construction requires approved safety cans or DOT containers for 5 gallons or less (1926.152(a)(1)); general industry’s quantity and storage rules in 1910.106 are written around approved safety cans.

What color safety can is for diesel?

Yellow by industry convention; red is gasoline, blue kerosene, green oil. The contents are labeled regardless.

How much gasoline can you store outside a cabinet?

25 gallons of Category 1 flammable liquid in containers per fire area outside a cabinet or storage room (1910.106(e)(2)(ii)(b), 1926.152(b)(1)).

How much can a flammable storage cabinet hold?

60 gallons of Category 1, 2 or 3 liquids or 120 gallons of Category 4, with no more than three cabinets per fire area.

Do you have to ground a safety can when filling it?

Category 1 and 2 liquids are dispensed only with the nozzle and container bonded (1910.106(e)(6)(ii)); the can sits on the ground, never in a truck bed liner.

The ratings, test results and standards shown here are the manufacturers' published values, reproduced as published. Nothing on this page is a recommendation by Bayshore Safety that any product is suitable for a particular task, hazard or workplace. Selecting safety products and protective equipment is the responsibility of the end user and the employer, based on their own hazard assessment and the regulations that apply to their work. Confirm every value on the manufacturer's own documentation before use.

Outfitting a yard, a shop or a truck for lifting and moving?Call (925) 215-7337 or email us the loads, the sizes and the quantities and we will quote slings, hardware, carts and cans with the part numbers listed. We sell nationwide.
All material handling and rigging guides

© 2026 Bayshore Safety & Industrial Supplies, Inc. All rights reserved. This guide may not be copied or republished without written permission.

How to buyCard, purchase order or invoice terms; quotes on request; agencies and institutions welcome.
Live Service & SupportReal people who know the products, Monday to Friday 7:30am to 4pm Pacific. 925-215-7337
We DeliverWe ship nationwide. Parcel and LTL freight to job sites and businesses across the U.S.