Skip to main content
Home › Guides › Fire extinguishers › NFPA 10 requirements
Guide · NFPA 10 (2026) · Fire extinguishers

NFPA 10 fire extinguisher requirements explained: selection, placement, mounting height, inspection and testing (2026 edition)

NFPA 10, Standard for Portable Fire Extinguishers, is the document OSHA (29 CFR 1910.157) and the fire codes adopt for how extinguishers are chosen, placed and kept. The current edition is 2026 and NFPA lets anyone read it free online. In plain words it says: pick extinguishers listed for the classes of fire present, with Class A building protection everywhere (5.5.2), Class B, C, D or K where those hazards exist (5.5.3), Class C-listed types and no dry chemical for delicate electronics (5.5.4.6), and halogenated agents only in rooms at least the nameplate minimum volume (5.3.2.6.1). Place them so no one walks more than 75 ft to a Class A unit or 30 to 50 ft to a Class B unit (Tables 6.2.1.1, 6.3.1.1), hung on a manufacturer bracket or in a cabinet (6.1.3.4) with the top no more than 5 ft up for units under 40 lb (6.1.3.9), visible or signed (6.1.3.3). Inspect monthly (7.2), maintain yearly with a tag (7.3.1.1, 7.3.4), examine internally and hydrotest on the type's interval (Tables 7.3.3.1, 8.3.1), and retire nonrechargeable units at 12 years (7.3.6.3).

Bayshore Safety. Industrial safety and PPE supplier since 2017. · Current as of November 2026 · NFPA 10 (2026) Chapters 5, 6, 7 and 8, sections as cited; OSHA 29 CFR 1910.157

Why does NFPA 10 matter if it is "only a standard"? Because the fire code your city adopted (the International Fire Code or NFPA 1) and OSHA 1910.157 point to it for the details. The inspector checks placement and tags against NFPA 10; the architect writes the spec to it; the insurer asks for the maintenance records it requires. The authority having jurisdiction (3.2.2) decides how it applies to your building, and state amendments exist.

NFPA 10 (2026) in seven questions

Each answer names its section.

Which classes do I need? (Chapter 5)Class A everywhere as building protection (5.5.2); B, C, D, K where present (5.5.3). Multi-letter units count for each letter (5.5.1). Delicate electronics: Class C-listed, no dry chemical (5.5.4.6).
How many and how far apart? (Chapter 6)Class A: 2-A minimum, 75 ft travel, one per 11,250 sq ft or less (Table 6.2.1.1). Class B: 5-B at 30 ft or 10-B at 50 ft for light hazard, more for ordinary and extra (Table 6.3.1.1). Class C sized on the A or B hazard (6.4.3). Class K within 30 ft (6.6.2).
How is it mounted? (6.1.3)Manufacturer hanger or bracket, listed bracket, or approved cabinet; never field-made (6.1.3.4). Top no more than 5 ft above the floor under 40 lb, 3.5 ft over 40 lb, bottom at least 4 in (6.1.3.9). Instructions face out (6.1.3.10).
How often is it inspected? (7.2)When placed in service and monthly: seven items (7.2.2). Records for the last 12 months (7.2.4).
How often is it maintained? (7.3)At least yearly by a trained person, with a tag showing month, year, person and agency (7.3.1.1, 7.3.4). Internal examination by type: 1, 3, 5 or 6 years (Table 7.3.3.1). Six-year teardown for stored-pressure units with a 12-year hydro (7.3.6).
When is it hydrotested? (Chapter 8)5 years (water, foam, CO2, wet chemical, stainless dry chemical) or 12 years (dry chemical mild steel, halogenated, dry powder) per Table 8.3.1. Nonrechargeable units are never tested; they are replaced at 12 years (7.3.6.3).
What is it listed to? (4.1)UL 711 for rating plus the type standard: UL 299 dry chemical, UL 154 CO2, UL 626 water, UL 2129 halocarbon clean agent (4.1.1).
Placement numbers from NFPA 10 (2026)
HazardMinimum ratingMaximum travel distanceSection
Class A, light or ordinary hazard2-A75 ftTable 6.2.1.1
Class A, extra hazard4-A75 ftTable 6.2.1.1
Class B spill, light hazard5-B or 10-B30 ft or 50 ftTable 6.3.1.1
Class B spill, ordinary hazard10-B or 20-B30 ft or 50 ftTable 6.3.1.1
Class B spill, extra hazard40-B or 80-B30 ft or 50 ftTable 6.3.1.1
Class CSized on the A or B hazardAs for A or B6.4.3
Class DPer the metal75 ft6.5.2
Class KListed for K30 ft6.6.2

Source: NFPA 10 (2026), sections as cited. Occupancy hazard classes are defined in 5.4.

Extinguishers by class

14 items · prices live

Ratings as published by the manufacturer. Prices are live.

ItemRatingPart numberPrice
Amerex 28084 Model 551 Halotron BrX Clean Agent Fire Extinguisher, 12.5 lb
Rating2A:10B:CPart28084
$1,431.84
Amerex 15510 Model 398 Halotron I Clean Agent Fire Extinguisher, 15.5 lb
Rating2A:10B:CPart15510
$2,256.25
Amerex 15509 Model 397 Halotron I Clean Agent Fire Extinguisher, 11 lb
Rating1A:10B:CPart15509
$1,570.75
Amerex 01714 Model 330 Carbon Dioxide Fire Extinguisher, 10-B:C, 10 lb
Rating10-B:CPart01714
$459.95
Amerex 01708 Model 332 Carbon Dioxide Fire Extinguisher, 10-B:C, 20 lb
Rating10-B:CPart01708
$686.96
Amerex 27702 Model C272 Water Mist Fire Extinguisher, 2-A:C, 2.5 Gallon
Rating2-A:CPart27702
$344.59

ItemRatingPart numberPrice
Amerex B456 Model ABC Dry Chemical Fire Extinguisher, 4A:80B:C, 10 lb
Rating4A:80B:CPartB456
$126.52
Amerex 15310 Model B500T ABC Dry Chemical Fire Extinguisher, 2A:10B:C, 5 lb
Rating2A:10B:CPart15310
$87.67
Amerex B500 Model ABC Dry Chemical Fire Extinguisher, 2A:10B:C, 5 lb
Rating2A:10B:CPartB500
$84.59
Amerex 15217 Model B417T ABC Dry Chemical Fire Extinguisher, 1A:10B:C, 2.5 lb
Rating1A:10B:CPart15217
$62.95
Amerex 11213 Model A411 ABC Dry Chemical Fire Extinguisher, 10A:120B:C, 20 lb
Rating10A:120B:CPart11213
$239.81

Cabinets, brackets and signs are in Fire protection accessories.

Questions people ask

What is NFPA 10?

The NFPA standard for the selection, installation, inspection, maintenance, recharging and hydrostatic testing of portable fire extinguishers. Current edition 2026; free to read on nfpa.org.

Is NFPA 10 required by law?

It becomes enforceable where a fire code or OSHA adopts it; OSHA 29 CFR 1910.157 references it for workplaces. Your authority having jurisdiction decides which edition applies.

How far apart must fire extinguishers be?

Class A: no more than 75 ft of travel to one; Class B: 30 or 50 ft by rating; Class K: 30 ft (NFPA 10 (2026) 6.2, 6.3, 6.6).

How high should a fire extinguisher be mounted?

Top no more than 5 ft above the floor for units up to 40 lb, 3.5 ft for heavier units, bottom at least 4 in (6.1.3.9).

How often does NFPA 10 require inspection?

Monthly after being placed in service (7.2.1); maintenance at least once a year (7.3.1.1).

What does NFPA 10 say about server rooms?

Delicate electronic equipment is protected by Class C-listed types and not by dry chemical (5.5.4.6); halogenated units follow the nameplate minimum room volume (5.3.2.6.1).

The ratings, test results and standards shown here are the manufacturers' published values, reproduced as published. Nothing on this page is a recommendation by Bayshore Safety that any product is suitable for a particular task, hazard or workplace. Selecting safety products and protective equipment is the responsibility of the end user and the employer, based on their own hazard assessment and the regulations that apply to their work. Confirm every value on the manufacturer's own documentation before use.

Specifying clean agent extinguishers for a project?Call (925) 215-7337 or email us with the room sizes and the spec section. We sell nationwide.
Clean agent fire extinguishers
How to buyCard, purchase order or invoice terms; quotes on request; agencies and institutions welcome.
Live Service & SupportReal people who know the products, Monday to Friday 7:30am to 4pm Pacific. 925-215-7337
We DeliverWe ship nationwide. Parcel and LTL freight to job sites and businesses across the U.S.