Skip to main content
Fire Extinguishers · Clean Agent · Amerex HT Series

Amerex HT Series Halotron BrX Clean Agent Fire Extinguishers

The Amerex HT Series is the commercial Halotron BrX clean agent line: four nonrechargeable units from 1.79 lb to 12.5 lb, listed to UL 2129 and UL 711, each with a 12-year service life and a wall or vehicle bracket in the box. Below: every unit with a live price, the specifications side by side, which unit fits which room volume under NFPA 10 (2026) 5.3.2.6.1, and what inspection and maintenance the standard asks for. Ships in 1–2 business days; most orders arrive in 3–7 business days.

HT Series Halotron BrX units

Part numberItemVersionPrice
28084Amerex 28084 Model 551 Halotron BrX Clean Agent Fire Extinguisher, 12.5 lb12.5 lb, 2A:10B:C, hose, steel$1,431.84

Source: Amerex HT Series clean agent sheet. Prices are live.

HT Series specifications side by side

Item551549547A537TS
Part number28084282042820228207
UL and ULC rating2A:10B:C5B:C5B:C2B:C
Capacity12.5 lb3.75 lb3.75 lb1.79 lb
DischargeHose and nozzleHose and nozzleNozzleNozzle
Range15 to 17 ft10 to 12 ft10 to 12 ft7 to 8 ft
Discharge time16 sec9 sec9 sec9 sec
CylinderSteelAluminumAluminumAluminum
Operating pressure150 psig100 psig100 psig90 psig
Height x width x depth20.25 x 8.5 x 5 in17.59 x 5.88 x 3.25 in17.59 x 4 x 3.25 in11.25 x 4 x 3.25 in
Shipping weight19.88 lb5.04 lb4.79 lb3.87 lb
Minimum room volume2,988 cu ft896 cu ft896 cu ft427 cu ft
Included bracketWallWallWallVehicle
RechargeableNo. 12-year service life; 6-year warranty
Temperature range-40 F to 120 F
StandardsUL 2129 / CAN/ULC-S566; UL 711 / CAN/ULC-S508; NFPA 10

Source: Amerex HT Series clean agent sheet; Halotron BrX information sheet; Amerex Halotron BrX owner's maintenance manual P/N 27192.

Which HT Series unit fits the room

NFPA 10 (2026) 5.3.2.6.1 requires that portable extinguishers containing halogenated agents be placed in line with the minimum room volume warning on the nameplate. Multiply the room's length, width and height in feet to get its volume in cubic feet, then pick a unit whose minimum is at or below that number.

Room volumeHT Series units Amerex lists for itExample room
Under 427 cu ftNone in the HT SeriesCloset-sized spaces
427 to 895 cu ftA537TS (2B:C)A 10 x 10 ft room with a 9 ft ceiling (900 cu ft is just over)
896 to 2,987 cu ft547 or 549 (5B:C), A537TSA 12 x 15 ft room with a 10 ft ceiling (1,800 cu ft)
2,988 cu ft and up551 (2A:10B:C), 547, 549, A537TSA 20 x 15 ft room with a 10 ft ceiling (3,000 cu ft)

Source: Amerex HT Series clean agent sheet minimum confined space requirements; NFPA 10 (2026) 5.3.2.6.1. Where a Class A rating is required for the room, only the 551 carries one.

Electronic equipment and energized electrical

NFPA 10 (2026) 5.5.4.6 directs that extinguishers protecting delicate electronic equipment be of a type listed and labeled for Class C, and that dry chemical extinguishers not be installed for that purpose. 6.4 requires Class C-rated units where energized electrical equipment can be encountered and sizes and locates them on the Class A or Class B hazard present. Amerex lists the HT Series for healthcare, clean manufacturing, data processing centers and museums.

Inspection and maintenance

Amerex states that stored-pressure Halotron BrX extinguishers do not require an internal examination of the cylinder or agent at annual maintenance, only a thorough external examination, and are replaced at 12 years from the date of manufacture on the nameplate. NFPA 10 (2026) does not require an annual internal examination for nonrechargeable extinguishers (7.3.3.6) and does not require a six-year internal examination or a hydrostatic test for them; they are removed from service no later than 12 years from the date of manufacture (7.3.6.3). Monthly inspection (7.2) and annual maintenance with a tag (7.3.1.1, 7.3.4) still apply, and the seal on a nonrechargeable unit is not removed (7.3.2.2.2). Check the code adopted by your authority having jurisdiction.

Amerex Halotron I units

Amerex also lists Halotron I (HCFC-123) units, which are rechargeable and carry a 6-year internal examination and a 12-year hydrostatic test under NFPA 10 (2026) Tables 7.3.3.1 and 8.3.1.

Part numberItemVersionPrice
15510Amerex 15510 Model 398 Halotron I Clean Agent Fire Extinguisher, 15.5 lb15.5 lb$2,256.25
15509Amerex 15509 Model 397 Halotron I Clean Agent Fire Extinguisher, 11 lb11 lb$1,570.75
15271Amerex 15271 Model B386T Halotron I Clean Agent Fire Extinguisher, 5 lb5 lb$770.98
15231Amerex 15231 Model B385TS Halotron I Clean Agent Fire Extinguisher, 2.5 lb2.5 lb$429.51
14400Amerex 14400 Model A384T Halotron I Clean Agent Fire Extinguisher, 1.4 lb1.4 lb$300.35

Source: Amerex Halotron I product data.

Guides: Halotron I vs Halotron BrX · clean agent extinguishers for data centers · minimum room volume · NFPA 10 for nonrechargeable units · Class C fire extinguishers.

Amerex HT Series questions

What is the Amerex HT Series? Amerex's commercial line of Halotron BrX (2-BTP) clean agent portable extinguishers: Models 551 (12.5 lb, 2A:10B:C), 549 and 547 (3.75 lb, 5B:C) and A537TS (1.79 lb, 2B:C), listed to UL 2129 and UL 711, nonrechargeable with a 12-year service life.

Which HT Series unit has a Class A rating? Only the 551 (2A:10B:C). The 547, 549 and A537TS are B:C rated.

What is the minimum room volume for each HT Series unit? 551: 2,988 cubic feet; 547 and 549: 896 cubic feet; A537TS: 427 cubic feet, per Amerex. NFPA 10 (2026) 5.3.2.6.1 makes the nameplate minimum a placement requirement.

Do HT Series extinguishers need a six-year teardown or hydrostatic test? No. NFPA 10 (2026) 7.3.6.3 exempts nonrechargeable extinguishers from the six-year internal examination and hydrostatic test; they are removed from service at 12 years from the date of manufacture.

What is the difference between the 547 and the 549? Same agent, capacity and rating; the 547 discharges through a nozzle on the valve and the 549 through a hose and nozzle.

Does each unit ship with a bracket? Yes. The 551, 549 and 547 ship with a wall bracket; the A537TS ships with a vehicle bracket. Amerex sells the Model 809 vehicle bracket for the 551 separately.

Is Halotron BrX accepted by the EPA? Amerex lists Halotron BrX as acceptable under the EPA Significant New Alternatives Policy (SNAP) program, with a GWP of 0.26 and an ODP of 0.0028.

The ratings, test results and standards shown here are the manufacturers' published values, reproduced as published. Nothing on this page is a recommendation by Bayshore Safety that any product is suitable for a particular task, hazard or workplace. Selecting safety products and protective equipment is the responsibility of the end user and the employer, based on their own hazard assessment and the regulations that apply to their work. Confirm every value on the manufacturer's own documentation before use.

How to buyCard, purchase order or invoice terms; quotes on request; agencies and institutions welcome.